How should the diesel generators and center control room be designed?

wps_doc_0

In civil buildings, particularly commercial functions, diesel generators should be found at the bottom. When there are special requirements for noise, resonance, and smoke, or where there is no ideal area in the space, you can select a reduced sound box diesel generator. Maintain a certain distance from the building to fulfill the application needs of special occasions. Below are eight preventative measures for diesel generator rooms.
1. In the computer space, except for the cooling water tank, various other layout requirements, please design based on the "Code for Civil Design Electric Design" JGJ/T16 -92 Table 6.1.3.2. When the distance in between the radiator as well as the wall is less than 250mm, the hot air can be directly released right into the wall. When the radiator water storage tank is 600-1000mm from the wall, the airplane cover is installed to release the warm air exterior, and also the adaptable adapter is included in between the aircraft cover and also the warmth dissipation water container. The web height of the generator terminal is typically two times the elevation of the generator set, at the very least 1.5 m greater than the generator.
2. Some industrial generator set need to mount everyday gas tanks. The ability of the day-to-day fuel storage tank usually fulfills 3 to 8 hrs. The everyday gas storage tank should be more than the diesel pump, and the brace can be set up. The outlet needs to be greater than 100mm more than all-time low of the can to stop pollutants from obstructing the pipe.

wps_doc_1

3. When the motor power is above 500kW, it is advised to set up a 16 #workmanship for installment of the training tools under the roof above the system.
The fire division in some areas have to purely strictly specify the ability of the day-to-day fuel tank (have absolutely nothing to do with the capability of the generator). The day-to-day gas storage tank have to be set up in a different fire area and geared up with an accident fuel storage tank. To this end, you need to pick up from the pertinent divisions. If necessary, lay out underground oil tank outdoors, to make sure that the exterior gas can speed up a particular amount of time after unloading.
4. General manufacturing plants provide the exhaust volume of each diesel-fueled generator device. According to the concept of higher than the amount of air volume than the displacement volume, the efficient location of getting in and leaving the windmail home window can be obtained. Given that the generator space is generally on the first stage, there ought to suffice vertical winding, which is conducive to sounding noise. The entry gate is usually situated at the backside of the generator, and also the exhaust gate is located in the position corresponding to the entry gateway. If it lies in the basement, it is hard to meet the above demands, but the warm air secreted ought to not be breathed in into the indoor fresh air tool, otherwise it can not be constructed from fresh air, cleansing and also cooling.
Keep in mind: The radiation home heating given off by generators, diesel motor engines as well as exhaust pipelines should additionally be mechanically ventilated or naturally aerated.
5.Emergency (extra) diesel generator collections, generally do not have independent control rooms.

wps_doc_2

6. Quiet diesel engine set exhaust gas has the characteristics of huge noise, large vibration, as well as heat. The pipe ought to be linked in the interior part. The interior "tapped muffler" is conducive to lowering sound as well as preventing contamination for outdoor or flue. Due to the high smoke temperature (regarding 500 ° C), normal clay floor tiles can not be durable, as well as refractory blocks need to be made from refractory blocks. The steel tube ought to be maintained insulation, as well as the surface temperature of the insulation layer does not exceed 60 ° C.
Note: Diesel engine tail gas emissions and dirt elimination, please consult the neighborhood environmental management division.
7. All diesel generator power stations other than the ground need to mount noise -soaking up products. The internal wall surface of the machine room is equally filled with rock wool in the permeable plate development, sound insulation, fire resistant. On top of that, going into as well as exhaust can effectively soak up audios and also reduce sound through the exhaust area as well as air intake area.
8. The structure of diesel generator machine collections is normally 200 concrete structures. The basis length as well as size are the common framework length of the unit. The width is 200-300mm. The structure is 50 to 200mm more than the ground.
H-Basic density (M).
K-weight several 1.5 G2.
G-Power Generation Overall Weight (KG).
D-concrete thickness 2400kg/mm3.
B-Base Width (M).
L-base length (m).
Foot screw holes are not reserved by the team. During the installment, the shock absorbers (or rubber shock absorbing pads) are put under the chassis of the device, and the shock absorbers are fixed with the structure with development bolts. If necessary, the seismic groove can be established around the foundation to supply much better defense for the structure. The trench width is 25-30mm, as well as the depth of the ditch is equal to the structure. The ditch is loaded with yellow sand or sawdust, or a blend of both.